Dry-Type Transformer Temperature Controllers
Dry-Type Transformer Temperature Controller

Model: Panel-mounted type

Three Pt100 inputs for dry-type transformer windings, with fan control, alarm/trip signals and front-panel temperature settings.

Technical Specifications

Temperature sensorsThree Pt100 platinum resistance sensors
Measuring range-30 to 200 °C
Measuring accuracy0.5% FS ±1 digit
Resolution0.1 °C
Auxiliary power supply176–242 V AC; 50 Hz
Power consumption5 VA
Controller weight<1 kg
Overall dimensions160 (W) × 80 (H) × 134 (D) mm
Panel cutout152 (W) × 76 (H) mm
Output arrangementConfirm the fan-output arrangement and alarm/trip contact load ratings for the ordered configuration

Key Features

Applications

Temperature monitoring of air-cooled dry-type transformer windingsCooling-fan control for dry-type transformersAlarm/trip signalling to external transformer control circuits

Product Description

Product overview

This panel-mounted controller monitors the three phase windings of an air-cooled dry-type transformer using Pt100 sensors. Switch between sequential phase temperatures and the highest winding temperature. The front panel provides temperature indication, status indicators and setting keys.

Temperature monitoring and control

  • Temperature settings: Set fan-on, fan-off, alarm and trip thresholds from the front panel. Protection settings should match the transformer requirements.
  • Fan control: Automatic operation responds to the temperature settings. Manual start/stop and periodic fan operation are also provided.
  • Alarm and trip: At the respective alarm and trip thresholds, the controller provides indication and switching signals to the external control cabinet. The external trip circuit performs the power-disconnection function.
  • Sensor fault: Fault indication and audible warning help identify an affected sensor. Confirm fault-output availability for the selected fan-output arrangement.
  • Records and testing: Configured settings are retained through power loss. Review stored power-loss winding-temperature records. Simulated temperature testing is provided for checking control functions; use the applicable instructions when planning commissioning tests.

Specify the required configuration

Use the technical specifications to check the auxiliary supply, temperature range and panel fit. Then specify the fan supply, number of fans and total rated current, together with the required alarm/trip circuit. Confirm the output arrangement, contact load ratings and final order code for the quoted unit.

Installation and technical documents

Check the panel cutout and available installation depth before ordering. Request the confirmed terminal diagram and installation information for the selected controller, Pt100 sensor assembly and fan arrangement. Confirm which sensors, cables and mounting accessories are included in the quotation.

Request a quotation

Send the transformer application, auxiliary supply, sensor requirements, fan voltage and total current, required alarm/trip settings, installation constraints, quantity and destination. Include any project-specific monitoring requirements for review.

Email your requirements