Low Voltage Power Factor Correction & Power Quality Solutions
APF Active Power Filter Device

Model: HY-APF-100/400-C

APF Active power filter device integrates one or multiple active power filter modules, a control unit, circuit breakers, contactors, a cooling system, and other core components into a standard industrial enclosure, forming a complete, plug-and-play harmonic mitigation solution.

Technical Specifications

Compensating capacity50A/100A/150A/200A/300A(customizable)module,cabinet type free parallel expansion capacity
Connection mode3-phase 3-wire/3-phase 4-wire
Operating voltage380V(-40%~+20%)
380V(-40%~+20%)50Hz(-10%~+10%)
System efficiency>97%
Filtering capabilityTHDi(current distortion rate )<5%
Filter range2nd to 50th order
Response time<300μS
Full response time<10ms
Neutral filter capability3 times that of phase lines
IGBT frequency30kHz(equivalent frequency)
Self-diagnosis and protection functionsYes
Communication interfaceRS232 RS485
Communication protocolModbus protocol
Installation methodWall-mounted / Rack-mounted
Class of protectionIP30
Lightning protection20kV
Number of Switching Operationsunlimited
CT transformer100/5~4000/5
Ambient temperature0℃ to 40℃
Storage temperature-20℃~70℃
Relative humidityMax 95%,non-condensing
Altitude≤ 1500m; between 1500m and 4000m, power derated by 1% per 100m according to GB/T 3859.2

Key Features

Applications

1.Industrial Motor Controls: APF diminish harmonics induced by motor operation, thereby boosting energy efficiency.2.Renewable Energy Grid Integration: APF streamline the output from fluctuating sources such as wind and solar, bolstering grid reliability.3.Commercial Buildings: APF enhance power quality for lighting and office equipment, reducing harmonic disruptions.4.Data Centers: APF guarantee a stable power supply for servers and network devices, optimizing energy utilization.5.Grid Transmission: APF are employed to minimize transmission losses, enhance voltage stability, and elevate power quality.

Product Description

Working principle

Its technical foundation is based on instantaneous reactive power theory and PWM (Pulse Width Modulation) technology.

1. Detection: External Current Transformers (CTs) continuously sample the load current signal in real-time.

2. Calculation: The built-in DSP (Digital Signal Processor) performs high-speed analysis on the sampled current, accurately calculating the harmonic, reactive, or negative-sequence current components that need to be compensated.

3. Generation and Injection: The controller drives the IGBT (Insulated-Gate Bipolar Transistor) power converter to generate a compensation current that is equal in magnitude and opposite in direction to the detected harmful current.

4. Cancellation: This compensation current is injected into the grid through a reactor, where it cancels out the harmonic currents generated by the load at the grid side. Ultimately, the current drawn from the grid becomes a clean sine wave.