AC-6b Capacitor Duty Contactor
Inrush Current Protection: Integrated resistors/Reactors limit switching surges.
our Detuned Harmonic Filter Reactors are built using premium, low-loss silicon steel cores, high-grade winding insulation, and precision engineering techniques.



Model: HY-DR-30-7-440
our Detuned Harmonic Filter Reactors are built using premium, low-loss silicon steel cores, high-grade winding insulation, and precision engineering techniques.

400V 14% 3P Detuned Harmonic Filter Reactor


Test result of 2 Detuned harmonic filter reactors in our production line as example:
Three-Phase Reactance / Inductance Balance:
This is the most critical quality index of the reactor, which directly determines three-phase current balance, temperature rise uniformity and filtering effect.
| Index | Reactor No.1 (Left) | Reactor No.2 (Right) | National/Industry Standard Requirement | Evaluation |
|---|---|---|---|---|
| Three-phase Reactance (Ω) | A: 0.5546 / B: 0.5622 / C: 0.5526 | A: 0.5476 / B: 0.5558 / C: 0.5452 | Deviation of each phase from the average value ≤ ±2% | Both units far exceed the standard |
| Maximum Relative Reactance Deviation | 1.37% | 1.53% | ≤ ±2% | No.1 performs better, and No.2 is also excellent |
| Three-phase Inductance (mH) | A: 1.7657 / B: 1.7900 / C: 1.7595 | A: 1.7441 / B: 1.7702 / C: 1.7365 | Deviation of each phase from the average value ≤ ±2% | Excellent consistency for both units |
| Maximum Relative Inductance Deviation | 1.37% | 1.53% | ≤ ±2% | Both are far below the national standard limit |
Active Power Loss
Lower power loss means less heat generation, longer service life and higher energy efficiency.
| Index | Reactor No.1 (Left) | Reactor No.2 (Right) | Conventional Industry Level | Evaluation |
|---|---|---|---|---|
| Total Three-Phase Loss ΣP | 0.1311 kW (131.1W) | 0.1382 kW (138.2W) | 150W ~ 200W | Both reach high-quality low-loss level |
| Maximum Single-Phase Loss | Phase B: 0.0443kW (44.3W) | Phase B: 0.0505kW (50.5W) | 60W ~ 70W | Superior loss control performance |
Voltage / Current Consistency
The parameters of the two products are highly similar, indicating that the production process and material selection are consistent.
| Reactor No.1 (Left) | Reactor No.2 (Right) | Evaluation | |
|---|---|---|---|
| Three-phase Voltage (V) | A: 19.275 / B: 19.550 / C: 19.325 | A: 19.169 / B: 19.429 / C: 19.185 | Highly balanced three-phase voltage with no obvious deviation |
| Three-phase Current (A) | A: 34.755 / B: 34.771 / C: 34.966 | A: 35.004 / B: 34.956 / C: 35.188 | Nearly identical three-phase current, further confirming excellent electrical symmetry |





Inrush Current Protection: Integrated resistors/Reactors limit switching surges.

APF Active power filter device integrates one or multiple active power filter modules, a control unit, circuit breakers, contactors, a cooling system, and other core components into a standard industrial enclosure, forming a complete, plug-and-play harmonic mitigation solution.

Dry-type iron-core reactors are critical electrical equipment in power systems, used for compensating capacitive reactive power, suppressing harmonic currents, and limiting short-circuit currents.