AC-6b Capacitor Duty Contactor
Inrush Current Protection: Integrated resistors/Reactors limit switching surges.
440V and 525V TÜV Rheinland certified cylindrical capacitor In accordance with IEC 60831-1&2:2014 standard Covering all required routine and type tests (including aging test).



Model: HY-TUV 400&525
440V and 525V TÜV Rheinland certified cylindrical capacitor In accordance with IEC 60831-1&2:2014 standard Covering all required routine and type tests (including aging test).
| Rated Voltage | 230V-900V |
|---|---|
| 1Phase/3 Phases | 3 Phases |
| Dielectric medium | Metalized Polypropylene Film |
| Rated Frequency | 50/60 Hz |
| Filling Material | Epoxy resin |
| Overvoltage | 1.1In |
| Test voltage (terminal/terminal) | 2.15UN/2S |
| Overcurrent | 1.3In |
| Test voltage, (terminal /casing) | 4000V/10/S |
| Capacitor casing | Stamped aluminum cans |
| Inrush current | 200IN |
| Capacitor type | Self-healing |
| Dielectric losses | Including resistor<0.5W/kvar Excluding resistor<0.2W/kvar |
| Internal disconnector | Have |
| Discharge resistor | external discharge resistor |
| Expansion lid | Have |
| Residual voltage after one minute | <120V |
| Tolerance on capacitance | ±5% |
| Discharge time | 3 minutes to 75V or less |
| OEM | Available |
| Ambient temperature category | -25~55℃ |
| Executive standard | IEC60831-1&2 2014 |
| Minimum installation gap | >30MM |
| Cooling | Natural air cooling |
| Humidity | <85% |
| Service life expectancy | ≥150000hours |
| Maximum switching time per year | 5000times |
| Mounting and Grounding | M12 or M16 Bottom bolt |


BKMJ 440V / 525V TUV Certified Reactive Power Compensation Capacitor:
The capacitors submitted for testing have passed IEC certification according to high standards. Unless customers specify special requirements, we do not guarantee that all capacitors are manufactured or delivered to IEC standards or above.
Selection form:


Dimension and outline


Inrush Current Protection: Integrated resistors/Reactors limit switching surges.

APF Active power filter device integrates one or multiple active power filter modules, a control unit, circuit breakers, contactors, a cooling system, and other core components into a standard industrial enclosure, forming a complete, plug-and-play harmonic mitigation solution.

our Detuned Harmonic Filter Reactors are built using premium, low-loss silicon steel cores, high-grade winding insulation, and precision engineering techniques.