Understand how the 85–265 V AC/DC wide supply range of the YHK-8000 simplifies cabinet design and spare-parts management.

1. What “85–265 V AC/DC” means in practice

A wide-range supply input accepts anything from 85 V to 265 V, on alternating or direct current, without a selector switch. In a switchgear cubicle this matters because the auxiliary supply is rarely clean: it may come from a station battery (110 V DC or 220 V DC), from a control transformer, or from a temporary generator during commissioning. A device with a fixed 230 V AC input needs a decision — and often an extra component — at each of those cases.

2. Fewer variants, smaller spare inventory

For a panel builder the visible saving is in the bill of materials. One part number covers both AC and DC cubicles, so the same unit can be fitted whether the project ends up with a battery-backed station or a simple transformer supply. For the end user the saving shows up years later: the spare in the store cupboard fits every cubicle in the substation, and a night-time replacement does not start with a question about the supply voltage.

  • One ordering code for AC and DC applications.
  • No selector link to set incorrectly during installation.
  • Replacement stock stays valid across sites with different auxiliary supplies.

3. Wiring and protection notes

A wide input does not remove the need for good practice. Keep the auxiliary circuit protected by a suitably rated miniature circuit breaker, separate the supply wiring from the CT and VT leads, and keep the earth reference clean. Because the input is a switching type, the inrush is short but real — where many devices share one breaker, check the total.

4. Where a wide supply is not the whole answer

Wide-range inputs solve the voltage question, not the continuity question. If the cubicle must stay supervised during a station battery discharge, the device supply has to sit on the protected bus, and the supervision host needs its own backup. Treat the wide input as flexibility at the device level, and design the auxiliary distribution at the system level.

Contact our technical team for the YHK-8000 wiring diagram and the recommended auxiliary protection arrangement for your cubicle.